GCS devices are suitable for power distribution systems in power plants, petroleum, chemical, metallurgy, textile, and high-rise buildings. In large power plants, petrochemical systems, etc., where automation is high and the interface with the computer is required, the three-phase AC frequency is 50(60)Hz, the rated working voltage is 380V (400V), (660V), and the rated current is 6300A and below. Low-voltage power distribution equipment for power distribution, power supply centralized control, and reactive power compensation in power supply and power supply systems.
Model meaning
Conditions of Use
● The altitude does not exceed 2000m;
● The ambient air temperature is not higher than + 40℃, and the average temperature within 24h is not higher than +35℃, and the ambient air temperature is not lower than -50℃;
● Atmospheric conditions: the air is clean, the relative humidity does not exceed 50% at a temperature of +40℃, and the higher relative humidity is allowed at a lower temperature, such as: 90% at +20℃;
● There is no fire, explosion hazard, serious pollution, chemical corrosion and severe vibration;
● It is inclined no more than 5° from the vertical plane;
● This product is suitable for the following temperature transportation and storage: -25℃ ~ +55℃, in a short time (not more than 24h) does not exceed +70℃.
Note: If the above conditions of use cannot be met, the user shall submit it to the manufacturer at the time of ordering and resolve it by negotiation.
The main technical parameters